Walk-Ins: The Importance of Equipment Placement

If you’re installing a walk-in cooler or freezer, it’s critical to make sure the condenser unit and evaporator coil are installed in the correct location. Choose the wrong spot and your customer could be looking at a difficult and expensive installation as well as performance issues from the entire system. No one wants those.

To avoid problems during and after the installation, discuss with your customer the ideal location for the condenser and evaporator coil. If it’s installed indoors, the condenser could take up valuable retail space. And if it’s outdoors, the ideal location for the unit could be inconvenient for maintenance or simply unpleasant to the eye. Choose a location that allows the customer to take best advantage of their space while not interfering with day-to-day operations.

If an indoor location is chosen for the condenser unit, keep ventilation and airflow in mind. It’s critical for operation. Plus, energy savings requirements have changed evaporator design. Newer evaporator motors ramp up and down, and this could create warm spots in walk-ins; also recent manufacturing requirements have changed as they relate to the distance from the back evaporator to the wall. Airflow requirements vary, so check with the manufacturer of your specific model. Most low-temperature units need around 200 CMF per 1,000 Btu/hr. A medium-temperature unit will call for 165 CFM per 1,000 Btu/hr. That means you’ll need a space that offers ample airflow — especially for a larger, more powerful unit. Indoors, the condenser can also generate heat. The presence of this extra hot air will need to factor into your decision-making process.

If installing outdoors, adequate ventilation shouldn’t be a problem. However, if you’re in a climate that often has very low temperatures, the condensing unit may need additional components such as a cycling control or a head pressure controller. These will help keep the high-side pressure above the minimum values when it’s cold out. Also, you can set up the system to use a pump-down method to control condensing unit operations and then add a crankcase heater, so refrigerant doesn’t migrate when it cycles off. Finally, your outdoor unit should be covered to protect it from the elements. You should check with the manufacturer to determine the best way to cover it.

As we all know, condenser units don’t work forever, so no matter if you install it indoors or outdoors, keep in mind that a tech will need to access it for service and routine maintenance. Make sure all parts of it are easy to access — after all, you may find yourself being the one performing the service on the unit.

Inside the walk-in, the location of the evaporator coil has a direct effect on its ability to keep the whole space at a consistent temperature. It’s critical to understand the total distance the evaporator needs to cover. This directly affects its performance. Check with the manufacturer of the evaporator for specific instructions, but don’t overlook the fact that the air pattern must envelop the entire room. Don’t install the coil where product could be stacked against it and block airflow. Make sure there’s enough space for storage and for normal business operations. It shouldn’t be in the way. Also, don’t install the unit over a door because it could draw in warm, humid air each time the door is opened—potentially leading to frost build-up.

Choosing the right location for all of the critical components of a walk-in cooler can help it run more efficiently. It can also make it easier to service or repair. Make sure to keep all of these things in mind for your next project to improve your HVACR technician skills.

 

Categories
Blog

Vacuum Pump and Vacuum Gauge – The HVACR power couple.

The use and placement of tools are critical to the success of maintaining or repairing HVACR systems. One misstep can lead to another, ultimately putting any system at risk and customers at a disadvantage when it comes to paying higher costs.

Whether you’re installing a whole new HVACR system or making repairs to an existing one, you need to evacuate the system before you can add new refrigerant. This means lowering the pressure down to a deep vacuum to ensure all moisture and non-condensable gasses are removed. If you don’t evacuate the system properly, moisture and non-condensable gasses that remain in the system will adversely affect system efficiency and may potentially lead to acid formation and critical component failure.

The best way to make sure that you pull a 500-micron vacuum, an industry-standard, is to use the ultimate power couple in HVACR service – the vacuum pump and vacuum gauge. Separately, they are amazing, powerful tools. Together, our best HVAC vacuum pump and best digital micron vacuum gauge offer a level of speed and accuracy that are truly game-changers for techs in the field.

To ensure that you’re using these tools correctly, keep these tips in mind:

1. Location, location, location: Choosing the placement of the vacuum gauge is key to pulling an accurate vacuum. Ideally, the vacuum gauge should be as far from the vacuum pump and connected at the system, preferably the service port, for a more accurate reading of the vacuum in the system. For a good single hose set up, consider installing the vacuum gauge on the liquid line and connecting the vacuum pump to the vapor line for optimal performance.

2. Clear every restriction: From small diameter hoses to valve cores, anything that restricts flow can slow down your evacuation. Before you start, remove the valve cores from the service port and use larger diameter vacuum-rated hoses to attach the pump. These will help speed up the entire process.

3. Know your readings: Today’s digital micron meters or vacuum gauges display instant, accurate data about pressure changes. When you’re pulling a vacuum, fluctuations in pressure are normal. Systems can take a while to equalize because there could be some outgassing or trapped moisture could be evaporating. Give the pump some time to work before you react to these minor fluctuations.

4. Use clean oil: If you’re removing a lot of moisture from a system, remember to replace the pump’s oil when it starts to look milky due to moisture or dirt. By always keeping the oil clean and dry, you allow the pump to maintain a greater pressure differential and pull a faster, deeper vacuum. Premium vacuum pumps allow the oil to be changed while the vacuum pump is running.

Pulling a vacuum to remove moisture and other impurities is part of life as a field technician in the HVACR industry. To thrive as a master of your trade, you need to know the right way to use a pump, the right way to place a vacuum gauge on your system and how to make HVACR’s power couple work best for you.